ABB ACS580 Series AC Inverter for 18.5kW (25HP) 400V 3 Ph motor to 37.7A at high overload, or 22kW (30HP) to 42.8A when Fan/Pump rated. Operates in VxF or Sensorless Vector control and converts fixed frequency Three Phase 400V input to variable frequency 400V to control the speed of a standard AC induction motor.
Dimensions: Size R3 206mm Wide x 236mm Deep x 490mm High (glandbox is integrated).
Enclosure Rated: IP55. (Option B056)
Weight: 14.9kg.
Overload: 150% x 60 seconds every 10 minutes (High Overload).
Overload: 110% x 60 seconds every 10 minutes (Fan/Pump rated).
Speed Control Range: 0-500Hz.
Braking: To 10 Ohm minimum, 22 Ohm maximum external resistor to 25kW (not supplied), see the Resistor options linked below or use the 'Which Resistor' button on this page.
Features: Supplied with Operator Keypad (Assistant Control Panel)
2 Analogue Inputs, 6 Digital Inputs, 2 Analogue Outputs, 3 Relay Contact Sets, terminals for RS-485/Modbus RTU communications, terminals for dual channel SIL3 safe torque off (STO), 24V AC/DC input to power the control unit when the main supply is disconnected.
Input Current: [as output current]
Input Voltage: 380-480V Three Phase +10% -15% at 50-60Hz ±5%
EMC Compliance: IEC EN61800-3:2004 + A1:2012 Category C2 (Industrial or restricted Domestic)
Mounting: Cubicle mount via 4 x 7.2mm diameter slotted holes at rear on 160mm x 473mm centres.
Ambient Temperature: Rated 40°C.
Ventilation space above: 200mm, below: 200mm, at sides: 150mm, in front: [Not Specified]
Heat Loss: 619W at maximum output.
New Part Number: ACS580-01-046A-4+B056 or 3AXD50000038980; Previous Part Number: ACS580-01-045A-4+B056, or 3AUA00000804**. Replaces ACS550-01-045A-4+B056
Download the ABB ACS580-01 Manual and Quick Start Guide from the links below:-