Teco E510s Series AC Inverter for 1.5kW (2HP) 400V 3 Ph motor in V/F or Sensorless Vector control to 3.8A. Converts fixed frequency three phase 400V input to variable frequency three phase 400V to control the speed of a standard AC Induction Motor or PM Synchronous Motor.
Frame: 1, 91mm Wide x 152mm Deep x 164mm High (excluding earth clamp).
Enclosure rating: IP20.
Weight: 1.5kg.
Output: 3.8A, 1.5kW at 400V
Overload: 150% x 60 seconds. 200% for 2 seconds
Speed Control Range: 0-599Hz
Braking (DBr): Built-in braking transistor. A 120 Ohm (minimum), 400 Ohm (100% braking torque) external resistor is required for Dynamic Braking. Resistor is not supplied and should only be fitted if this feature is required. Resistor option given below.
LED Keypad
Features: 2 Analogue Inputs, 6 Digital Inputs, 1 Analogue Output, 1 Relay Contact set, 1 NC Relay
Fieldbus: Modbus (RTU and ASCII) and BACnet communication interface included
Safety Function: STO (Safe Torque Off) Dedicated dual input up to SIL2, PLd (Linked out as default, remove links to add safety circuit)
Input Current: 3.8A
Input Voltage: 380-480V Three Phase +10% -15% at 50-60Hz
Short Circuit Rating: 5kA. Where supply transformer exceeds 600kVA, 3% Impedance AC Line Chokes are required.
10A Fast Acting Fuses or 15A MCCB are required (Operation must be fast enough to ensure Short Circuit rating is not exceeded)
EMC Filters (EMC): IEC EN61800-3 / EN61800-5-1 Class A Category C2 (Industrial and restricted Domestic). Can be disabled if required
Ambient: Rated 50°C.
Ventilation space in front: [not specified].
Ventilation space above and below: 120mm.
Ventilation space at sides: 50mm.
Heat Loss at max output: [not specified]
Manufacturer Part Number: E510-402-SH3F, also known as 11-201-43-402-30. Replaces: E510-402-H3F