Teco A510 Series AC Inverter for 5.5kW (7.5HP) 400V 3 Ph motor to 14.8A at high overload, or 7.5kW (10HP) to 17.5A when Fan/Pump rated. Operates in VxF, Sensorless Vector or Full Closed-loop Flux Vector (when the optional Encoder Feedback card is fitted). Converts fixed frequency three phase 400V input to variable frequency three phase 400V to control the speed of a standard AC induction motor or permanent magnet synchronous motor.
Dimensions: Size 2 140mm Wide x 177mm Deep x 349mm High.
Weight: 4.72kg.
Overload: 150% x 60 seconds, 200% x 2 seconds (High Overload).
Overload: 120% x 60 seconds (Fan/Pump rated).
Speed Control Range: 0-1200Hz (depending on control mode).
Braking: Minimum 130 Ohm minimum external resistor (not supplied), see the Resistor options linked below or use the 'Which Resistor' button on this page.
Features: 2 Analogue Inputs, 8 Digital Inputs, 1 Pulse Input, 2 Analogue Outputs, 2 Digital Outputs, 2 Relay Contact sets, 1 Pulse Output, 1 Safety Switch, RJ45 port for Modbus RS485 Communications.
Input Current: 15.5A (high overload), 18.2A (fan/pump rated).
Input Voltage: 380V-480V Three Phase +10% -15% at 50-60Hz ±5%, via 25A High Speed fuse.
EMC Filters: IEC EN61800-3 (Industrial).
Mounting: Wall mount in clean environment or cubicle mount via 4 x holes at rear for M5 screws on 124mm x 266mm centres.
Ambient: Rated 40°C.
Ventilation space in front: [not specified], Ventilation space above and below: 150mm, Ventilation space at sides: 200mm.
Heat Loss: [not specified].
Part Number: A510-4008-H3F.
Download the Teco A510 Manual and Quick Start Guide from the links below:-