Parker 890SD AC Frequency Inverter for 132kW (177HP) 400V 3 Ph motor to 250A at constant torque (Heavy Duty), and 150kW (200HP) Quadratic Torque to 302A. Suitable for a Standard AC Induction Motor in VxF, Sensorless Vector Control or Full Closed Loop Vector Control with an optional Speed Feedback Card. Also suitable to control a PM Brushless AC Servo Motor when fitted with an optional Feedback Card. (See Feedback Options below)
Simple set-up and ready to run in VxF from its default settings.
Requires external choke - part number CO389936U401 (not included)
Advanced Performance: (Advanced features now included as standard, originally optional). Includes Basic LINK VM function blocks: math functions, Boolean logic, timers, counters, One shots, threshold comparators, latches, plus: motion control firmware with added position loop, motion control function blocks, move incremental, move absolute, move home, line drive master ramp and section control, winder blocks (SPW, CPW), full function PID, state machine, and others
Size G - 455mm Wide x 465mm Deep x 1042mm High plus space required at sides for bars and above for roof mounting fan.
Weight - 108kg
Overload - 150% x 60 seconds and 180% for 1 second (V/F mode) for constant torque. 110% for 60 seconds (V/F mode) for quadratic torque
Switching frequency - 2.5kHz at full output.
Speed Control Range - 0/120Hz at continuous rating.
Brake Switch not included included.
4 x Analogue Inputs, 9 Digital Inputs, 2 Analogue outputs, 2 Digital outputs, 1 set of volt free relay output contacts.
Input Current - 216A at 400V (constant torque), 297A at 400V (quadratic torque).
Input Voltage - 380/460V three phase +-10% at 50/60Hz. +-5%
Input fuse - 300A at high overload or 350A when Fan/Pump rating set - to suit input bridge at 304000A²s
Cubicle mounting.
Rated at 40C Ambient.
Ventilation fan requires a separate 230V supply fused at 2A.
Total Power Loss at max output - 2912W (constant torque), 3482W (quadratic torque).
Option Modules were originally supplied fitted to the 890CD, Modules are now supplied as additional items (Please see linked items below).
Additional option cards are required to achieve the variants given below:
Part Number Variation in block 4 (Legacy Part Variations in blocks 10): 1(E1), 3(EQ), 5(RE), 6(RR), 7(M1), L(LS) eg 890SD-531200B0-B00-1A300 (890SD/5/0002B/0/00/A/UK/00/00/EQ/00/00) was supplied with an Encoder Feedback Option card 8902-EQ-00 fitted.
Part Number Variation in block 4 (Legacy Part Variations in block 11): N(CB), C(CN), D(DN), H(IP), T(IM), P(PB), 7(M1), S(RS), K(CT), E(EP) eg 890SD-53120000-B00-1A0P0 (890SD/5/0002B/0/00/A/UK/00/00/00/PB/00) was supplied with Profibus Communications Card 8903-PB-00 fitted
Full part number is - 890SD-433250G2-000-1A000 (was - 890SD-4-0250G-0-2F-A-UK-00-00-00-00-00). - Exactly the same as SSD Drives and Eurotherm Drives.