ABB ACS580 series AC Inverter for 7.5kW (10HP) 400V 3 Ph motor to 17A at high overload or 11kW (15HP) to 23.8A when Fan/Pump rated. Operates in VxF or Sensorless Vector control and converts fixed frequency Three Phase 400V input to variable frequency 400V to control the speed of a standard AC induction motor.
Size R2: 125mm Wide x 239mm Deep x 503mm High. IP55.
Weight: 6.7kg.
Overload: 150% x 60 seconds every 10 minutes (High Overload)
Overload: 110% x 60 seconds every 10 minutes (Fan/Pump rated)
Speed Control Range: 0-500Hz.
Braking: To 22 Ohm minimum, 52 Ohm maximum external resistor to 10kW (not supplied) - See the Resistor options linked below or use the 'Which Resistor' button on this page.
Supplied with Operator Keypad (Assistant Control Panel)
2 Analogue Inputs, 6 Digital Inputs, 2 Analogue Outputs, 3 Relay Contact Sets, terminals for RS-485/Modbus RTU communications, terminals for dual channel SIL3 safe torque off (STO), 24V AC/DC input to power the control unit when the main supply is disconnected.
Input Current: [as output current]
Input Voltage: 380-480V Three Phase +10% -15% at 50-60Hz ±5%
EMC Compliance: IEC EN61800-3:2004 + A1:2012 Category C2 (Industrial or restricted Domestic)
Cubicle mount.
Rated 40°C Ambient.
Ventilation space above: 30mm, below: 200mm, at sides: 150mm, in front: [Not Specified]
Heat Loss at max output: 322W
Mounting via 4 x 6.5mm diameter slotted holes at rear on 98mm x 417mm centres.
New Part Number is ACS580-01-026A-4+B056 or 3AXD50000038977. Previous Part Number ACS580-01-025A-4+B056 or 3AUA0000083569. Replaces ACS550-01-023A-4+B055.
Download the ABB ACS580-01 Manual and Quick Start Guide from the links below:-