Universal GD200A Series AC Inverter for 0.75kW (1HP) 400V 3-phase motor to 2.5A at high overload. Operates in standard VxF or Sensorless Vector Control and Converts fixed frequency three phase 400V input to variable frequency three phase 400V to control the speed of a standard AC Induction motor.
Output Current: 2.5A
High Overload: 150% x 60 seconds; 200% x 1 second.
Dimensions: Size 1; 126mm Wide x 175mm Deep x 186mm High.
Enclosure Rating: IP20.
Weight: 1.8kg.
Speed Control Range: 0-400Hz
Braking (DBr): Internal Braking Switch fitted.
Braking Resistor (not supplied): 240 Ohm minimum – Fit resistor only if braking is required; see 'Brake Resistor Calculator' below.
Fixed Keypad with 5 x 7 segment LED display.
2 Analogue Inputs, 8 Digital Inputs, 2 Analogue Outputs, 1 Digital Output, 2 Relay Contact sets, 1 High Frequency Input (50kHz), 1 High Frequency Output (0-50kHz)
Twin wire connection for RS485 Communications. (Modbus ASCII & Modbus RTU protocols)
Input Current: 3.4A High Overload.
Input Voltage: Three Phase 380-440Vac (+10% -15%) 50/60Hz (47-63Hz)
EMC Filters: IEC EN61800-3 Second Environment (Industrial – C3).
EMC Filter may be disabled. J10 should be fitted to enable the EMC Filter.
Mounting: Cubicle mount via 4 x holes at rear for 5mm screws on 115 x 175mm centres.
Ambient: Rated at 40°C; 50°C Max with de-rate.
Ventilation space in front: [not specified], Ventilation space above and below: 100mm, Ventilation space at sides: 100mm.
Heat Loss at max output: Not given
Part number: GD200A-0R7G-4 (GD200A0R7G4)
Download the Universal GD200A Manual from the links below:-