WEG CFW900 Series AC Inverter for 5.5kW 400V 3 Ph motor to 12A at high overload, or 5.5kW to 14A when Fan/Pump rated. Operates in VxF, Sensorless Vector or Full Closed-loop Flux Vector (with encoder card fitted). Converts fixed frequency three phase 400V input to variable frequency three phase 400V to control the speed of a standard AC induction motor or PM synchronous motor.
Rating (HD): 4kW and 5.5kW, 12A, 8.3kVA with 150% Overload for 60 seconds every 5 minutes or 200% Overload for 3 seconds every 5 minutes
Rating (ND): 5.5kW, 14A, 9.7kVA with 110% Overload for 60 seconds every 5 minutes or 150% Overload for 3 seconds every 5 minutes
IP20
Frame A, 145mm Wide x 222mm Deep (158mm Deep when flange mounted) x 245mm High (334mm High with earth clamp)
Mounting via 4 x M5 fixings.
Weight: 4.5kg.
Speed Control Range: 0-500Hz
Dynamic Brake (DBr): Fitted with Internal Braking switch. Fit external baking resistor if this feature is required. Recommended resistance is 32 Ohm (not supplied). 25A Maximum. See braking resistor option below.
DC Bus terminals and DC link choke are fitted as standard.
Removable Keypad with Graphical Multi-line LCD display. (Cubicle mounting kit available).
Keypad is fitted with Bluetooth Interface for smart phone programming and diagnostics
2 x Analogue Inputs, 6 x Digital Inputs, 2 x Analogue Outputs, 2 x Digital Outputs, 3 x Relays (1 x Change-over, 2 x Normally Open)
Option Slots: 4 Slots available as standard, can be extended to 7 with optional expansion port.
PC programming via USB port. USB cable (not supplied), free WPS software required. (PC programming can be done without mains power)
Communication: Dual EtherNET and Modbus RTU fieldbus fitted as standard.
Soft PLC Included: WLP Free Software required.
SD Slot for Parameter and Soft PLC program storage (SD card not supplied)
Real Time Clock Included (CR 2032 Battery required)
Safety Features: Dedicated Dual Chanel input for STO (Safe Torque Off) and SS1-t (Safe Stop timed) Safety features. Please consult Safety Manual below for further details.
PCB Coating: 3C2
External 24V Supply: Controls can be powered from a separate 24V DC supply if required
Input Current: 12A (HD), 14A (ND). Input protection via 20A High Speed Fuse.
Input Voltage: 380-480V Three Phase +10% -15%, 50/60Hz (48-63Hz)
EMC Compliance (IEC/EN61800-3): Fitted with Internal EMC Filters, C3 (Industrial) Classification with motor cables up to 200m.
EMC Filter earth connection can be removed if required.
Cubicle or flange mount.
Rated Ambient: 50°C. (60°C Maximum with de-rate)
Minimum Ventilation Space: 25mm Top, 25mm Bottom, 0mm Between Units, 10mm Front.
Heat Loss at max output: 172W (HD), 201W (ND)
Standby Heat Loss: 48W
Efficiency at max output: 2.1% (at 90% motor frequency and 100% torque ); Ecodesign Classification: IE2
Extended Warranty Available: When purchased with a WEG W22 Motor (see linked products below) the warranty for the motor and the AC Inverter can be extended to 3 years. Terms and Conditions apply, registration process is required.
Manufacturer part number is CFW900A14P0T4DB20Y2B CFW900 is a new product that replaces the CFW11. Previous generation CFW11 0013T4 / 0017T4