WEG CFW700 Series AC Inverter for 90kW (120HP) 400V 3 Ph motor to 180A at high overload, or 110kW (150HP) to 211A when Fan/Pump rated. Operates in VxF, Sensorless Vector or Full Closed-loop Flux Vector. Converts fixed frequency three phase 400V input to variable frequency three phase 400V to control the speed of a standard AC induction motor or permanent magnet synchronous motor.
Size: Frame E, 335mm Wide x 358mm Deep x 675mm high. IP20
Weight: 65kg.
Output Current: 211A (ND), 180A (HD).
Overload: 150% x 60 seconds, 200% x 3 seconds (High Overload)
Overload: 110% x 60 seconds, 150% x 3 seconds (Fan/Pump rated)
Speed Control Range: 0-300Hz (depending on control mode)
Braking: None.
2 Analogue Inputs, 8 Digital Inputs, 2 Analogue Outputs, 4 Digital Outputs, 1 Relay Contact set, DC Bus Terminals, Terminals for Incremental Encoder, Terminals for RS485 Communications.
Input Voltage: 380-480V Three Phase +10% -15% at 50-60Hz ±3%
EMC Filter: Integrated, to IEC EN61800-3 Category C3 (industrial).
Safety Function: Safe Torque Off (STO) suitable in applications up to Cat. 3 / PL d acc. to EN ISO 13849-1 and SIL 2 acc. to IEC 62061 / IEC 61508.
Wall mount in clean environment or cubicle mount on or through a backplate.
Rated 45°C Ambient.
Ventilation space in front: 20mm, Ventilation space above: 100mm, Ventilation space below: 250mm, Ventilation space at sides: 80mm.
Heat Loss at max output: 1940W (High Overload), 2330W (Fan/Pump rated).
Mounting via 4 x M8 bolts at rear on 275mm x 635mm centres onto backplate, or through 315mm x 615mm backplate aperture.
Manufacturer part number is CFW700E0211T4NB20C3Y1 or 11877024.
Download the WEG CFW700 Manual, Parameter Reference and Programming Guide from the links below:-