SSD 690P AC Frequency Inverter for 250kW to 280kW (335HP to 375HP) 400V 3 Ph motor to 480A at high overload (Heavy Duty) or 300kW to 315kW (400HP to 425HP) to 545A when Fan/Pump rated, operates in VxF, Sensorless Flux Vector or Full Closed Loop Flux Vector control (when the optional encoder board is fitted).
(The output kW depends on supply Voltage and motor flc).
Simple set-up and ready to run in VxF from its default settings.
Requires external choke - part number CO389936U403 (not included)
Size H - 570mm Wide x 465mm Deep x 1180mm High plus space required at sides for bars and above for fan duct and roof mounting fan.
Weight - 125kg
Overload - 150% x 60 seconds and 180% for 0.5seconds at high overload rating or 110% for 10 seconds for fan/pump rating.
Switching frequency - 2.5kHz at full output, reducing to 1.2kHz at maximum overload.
Speed Control Range - 0/250Hz at continuous rating, or 120Hz if used to maximum overload.
Braking - none.
4 x Analogue Inputs, 8 Digital Inputs, 3 Analogue outputs, 3 Digital outputs (relay contacts).
Input Current - 466A at high overload or 545A when Fan/Pump rating set.
Input Voltage - 380/460V three phase +-10% at 50/60Hz.
Input fuse - 550A at high overload and 650A when Fan/Pump rating set - to suit input bridge at 813000A²s
Cubicle mounting.
Rated at 40C Ambient.
Ventilation fan requires a separate 230V supply fused at 4A.
Heat Loss at max output - 4984W at high overload and 5743W when Fan/Pump rating set.
Full part number is - 690-433480H2-000P00-A400 (was - 690PH-2500-400-0011-UK-0-0-0-0-00-230-0). - Exactly the same as SSD Drives and Eurotherm Drives - 690PH-2500-400-0011-UK-0-0-0-0-00-230-0.