CT Commander SK 55kW/75kW 400V 3ph AC Inverter Drive, DBr, C3 EMC

SK5401

Order Code: 19595
Obsolete Product
This item is now obsolete. Alternatives may be available - see linked products below.

Brand: Control Techniques, Range: Commander SK

Control Techniques Commander SK Series AC Inverter for 55kW (100HP) 400V three phase motor to 124A at High Overload or 75kW (100HP) to 138A when Fan/Pump rated. Operates in VxF or Sensorless Vector Control and converts fixed frequency three phase 400V Input to variable frequency three phase 400V to control the speed of a standard AC Induction Motor.

Size 5: 310mm Wide x 298mm Deep x 857.3mm High. IP20
Weight: 55kg.

Overload: 150% x 60 seconds from cold, 150% x 8 seconds from full load (High Overload)
Overload: 110% x 215 seconds from cold, 110% x 5 seconds from full load (Fan/Pump Rated)
Speed Control Range: 0-1500Hz
Braking: Minimum 7 Ohm, Average 82.5kW for 60 seconds external resistor (not supplied) - use the 'Which Resistor' button on this page.

1 Analogue Input, 1 Analogue/Digital Input, 4 Digital Inputs, 1 Analogue Output, 1 Digital Input/Output, 1 Relay Contact set, RJ45 port for Modbus.
Input Current: 126A (Fan/Pump Rated)
Input Voltage: 380-480V Three Phase ±10% at 50-60Hz ±5%
EMC Filters: EN 61800-3:2004 Second Environment (Industrial). Can be removed if required.

Wall mount in clean environment or cubicle mount.
Rated 40°C Ambient.
Ventilation space in front: [not specified].
Ventilation space above and below: 100mm.
Ventilation space at sides: 30mm.
Heat Loss at max output: 1311W (High Overload), 1471W (Fan/Pump rated) at ambient temperature and default switching frequency.
Mounting via 4 x 8.5mm diameter holes at rear on 258.6mm x 839.3mm centres.

Manufacturer part number is SK5401. Replaces Commander SE.

Download the Commander SK Manual and Guides from the links below:-