Mitsubishi FR-A800 Series AC Inverter for 250kW (335HP) 400V 3 Ph motor to 481A at high overload, or 315kW (420HP) to 610A when Fan/Pump rated. Operates in VxF, Sensorless Vector or Full Closed-loop Flux Vector (when the optional Encoder Feedback card is fitted). Simple set-up and ready to run from its default settings.
Overload: 150% x 60 seconds and 200% x 3 seconds at High Overload, or 110% x 60 seconds and 120% x 3 seconds when Fan/Pump Rated.
Dimensions: 680mm Wide x 380mm Deep x 1010mm High.
Protection: IP00.
Weight: 166kg
Speed Control Range: 0.5Hz to 400Hz.
Braking: None (option via external brake unit).
Features: 3 Analogue Inputs, 12 Digital Inputs, 2 Analogue Outputs, 5 Digital Outputs, 2 Relay Contact Sets, integrated PLC functions and Ethernet (Option card FR-CF80-01-E2-60 (V307205) is included.
'Safe Torque Off' (STO) function to SIL 2.
Input Current: 481A at high overload, or 610A when Fan/Pump rating set.
Input Voltage: 380V to 500V Three Phase +10% -15% at 50/60Hz ±5%
EMC Filters to BSEN61800-3 for the 2nd Environment (Industrial).
Mounting: Cubicle mount.
Ambient Temperature: -10° to 50°C (40° when Fan/Pump rated).
Ventilation space in front: 50mm
Ventilation space above and below: 200mm.
Ventilation space at sides: 100mm.
Mounting via 6 x 12mm diameter holes at rear on 300mm/600mm x 984mm centres.
Power Loss: 6650 Watts.
Includes DC Reactor type FR-HEL-H280K (273312) for mounting alongside.
Dimensions: 190mm Wide x 255 Deep x 440mm high.
Connections: 2 x lugs for M16 bolts.
Weight: 38kg.
Manufacturers Part Number: F800-FR-AF840-06100-E2-60 Includes FR-AF840-06100-60, FR-CF80-01-E2-60 (Ethernet Control card) and FR-HEL-H280K (DC Choke).