Mitsubishi FR-A800 E Series AC Inverter for 220kW (295HP) 400V 3 Ph motor to 432A at high overload, or 250kW (335HP) to 547A when Fan/Pump rated. Operates in VxF, Sensorless Vector or Full Closed-loop Flux Vector (when the optional Encoder Feedback card is fitted). Simple set-up and ready to run from its default settings.
Size 10 - 680mm Wide x 380mm Deep x 1010mm High. IP00 Weight: 166kg
Overload - 150% x 60 seconds, 200% x 3 seconds (High Overload)
Overload - 110% x 60 seconds, 120% x 3 seconds (Fan/Pump Rated)
Speed Control Range - 0.5Hz to 400Hz.
Braking – None (option via external brake unit).
Terminal CA Equipped Model.
3 Analogue Inputs, 12 Digital Inputs, 2 Analogue Outputs, 5 Digital Outputs, 2 Relay Contact Sets, integrated PLC functions and RS485 Modbus-RTU,
Includes Built-in Ethernet Board (FR-A8ETH).
Control Logic - Source Version.
Circuit Board Coated (Conforming to IEC60721-3-3 3C2/3S2).
'Safe Torque Off' (STO) function to SIL 2.
Input Current -432A at high overload or 547A when Fan/Pump rating set.
Input Voltage - 380-500V Three Phase +10% -15% at 50/60Hz ±5%
EMC Filters to BSEN61800-3 for the 2nd Environment (Industrial).
Wall mount in clean environment or cubicle mount.
Rated -10° to 50°C Ambient (40° when Fan/Pump rated).
Ventilation space in front 50mm
Ventilation space above and below - 200mm.
Ventilation space at sides – 100mm.
Mounting via 6 x 12mm diameter holes at rear on 600mm x 984mm centres
Includes separate DC Reactor (Choke): FR-HEL-H220K - (Failure to fit will cause damage to drive).
Full part number is - FR-A840-05470-E2-60 + FR-HEL-H220K (Replaces FR-A840-05470-2-60)