Mitsubishi FR-A800 E Series AC Inverter for 7.5kW (10HP) 400V 3 Ph motor to 17A at high overload, or 11kW (15HP) to 25A when Fan/Pump rated. Operates in VxF, Sensorless Vector or Full Closed-loop Flux Vector (when the optional Encoder Feedback card is fitted). Simple set-up and ready to run from its default settings.
Dimensions: Size 2 220mm Wide x 170mm Deep x 260mm High.
Enclosure rating: IP20.
Weight: 6.7kg.
Overload: 150% x 60 seconds, 200% x 3 seconds at High Overload rating.
Overload: 110% x 60 seconds, 120% x 3 seconds when Fan/Pump Rated.
Speed Control Range: 0.5Hz to 400Hz.
Braking: None (option is available via an external brake unit).
Terminal CA Equipped Model.
3 Analogue Inputs, 12 Digital Inputs, 2 Analogue Outputs, 5 Digital Outputs, 2 Relay Contact Sets, integrated PLC functions and RS485 Modbus-RTU,
Includes Built-in Ethernet Board (FR-A8ETH).
Control Logic - Source Version.
Circuit Board Coated (Conforming to IEC60721-3-3 3C2/3S2).
'Safe Torque Off' (STO) function to SIL 2.
Input Current: 22.5A at high overload or 31.7A when Fan/Pump rating set.
Input Voltage: 380V-500V Three Phase +10% -15% at 50/60Hz ±5%.
EMC Filters: to BSEN61800-3 for the 2nd Environment (Industrial).
Mounting: Cubicle mount via 4 x 6mm diameter holes at rear on 195mm x 245mm centres.
Ambient: Rated -10° to 50°C (40° when Fan/Pump rated).
Ventilation space in front: 50mm.
Ventilation space above and below: 100mm.
Ventilation space at sides: 50mm.
Part Number: FR-A840-00250-E2-60 (Replaces: FR-A740-00250-EC).
Download the A800 Manual and Installation Guide from the links below:-