Mitsubishi FR-A800 E Series AC Inverter for 0.4kW (0.5HP) 400V 3 Ph motor to 1.5A at high overload, or 0.75kW (1HP) to 2.3A when Fan/Pump rated. Operates in VxF, Sensorless Vector or Full Closed-loop Flux Vector (when the optional Encoder Feedback card is fitted). Simple set-up and ready to run from its default settings.
Size 1 - 150mm Wide x 140mm Deep x 260mm High. IP20 Weight: 2.8kg
Overload - 150% x 60 seconds, 200% x 3 seconds (High Overload)
Overload - 110% x 60 seconds, 120% x 3 seconds (Fan/Pump Rated)
Speed Control Range - 0.5Hz to 400Hz.
Braking – None (option via external brake unit).
Terminal CA Equipped Model.
3 Analogue Inputs, 12 Digital Inputs, 2 Analogue Outputs, 5 Digital Outputs, 2 Relay Contact Sets, integrated PLC functions and RS485 Modbus-RTU,
Includes Built-in Ethernet Board (FR-A8ETH).
Control Logic - Source Version.
Circuit Board Coated (Conforming to IEC60721-3-3 3C2/3S2).
'Safe Torque Off' (STO) function to SIL 2.
Input Current -2.3A at high overload or 3.2A when Fan/Pump rating set.
Input Voltage - 380-500V Three Phase +10% -15% at 50/60Hz ±5%
EMC Filters to BSEN61800-3 for the 2nd Environment (Industrial).
Wall mount in clean environment or cubicle mount.
Rated -10° to 50°C Ambient (40° when Fan/Pump rated).
Ventilation space in front 50mm
Ventilation space above and below - 100mm.
Ventilation space at sides – 50mm.
Mounting via 4 x 6mm diameter holes at rear on 125mm x 245mm centres.
Full part number is - FR-A840-00023-E2-60 (Replaces:- FR-A840-00023-2-60, FR-A740-00023-EC)
Download the A800 Manual and Installation Guide from the links below:-