Danfoss VLT FC-302 series AC Frequency Inverter for 5.5kW (7.5HP). 400V three phase motor in VxF control or Sensorless Flux control. Converts fixed frequency three phase 400V input to variable frequency three phase 400V to control the speed of a standard AC Induction motor or permanent magnet synchronous motor.
Frame Size A3: 268mm high x 130mm wide x 220mm deep. IP20.
Weight:6.8kg
Supply Voltage: 380Vac - 500Vac +/- 10%, 50/60Hz +/-5%.
Input current (380 - 440V): 11.7A continuous, 18.7A intermittent.
Continuous Output Current: 13A.
Overload: 160% for 60 seconds every 10 minutes.
Output frequency: 0 - 590Hz in V/F mode or 0 - 300Hz in Sensorless Flux Control.
Speed Control Range: 0 - 590Hz in VxF Control, 0 - 300Hz in Sensorless Flux Control.
Braking: Brake Switch Fitted.
Option B: MCB-101 General purp. I/O additional 3 digital inputs, 2 analog inputs, 2 digital outputs and 1 analog output.
Graphical Keypad, 2 x Analogue Inputs, 6 Digital Inputs, 1 Analogue outputs, 2 Digital/Pulse outputs, 2 Relay Outputs.
1 x Safe Torque Off Input, Category 3 to SIL2, SILCL2, performance level "d".
Programmable from a PC via USB and free Danfoss MCT 10 software (see download link below).
EMC Compliant to Class A2 (C3) Industrial Environment.
Cubicle mount.
Ventilation space above and below should be 100mm. Can be mounted flush to each other at either side.
Heat Loss is 187W at full load.
Rated at 45°C Ambient. See Design guide for de-ratings for higher temperatures.
Part number: 131B4427.
Type Code is: FC-302P5K5T5E20H2BGXXXXSXXXXAXBKCXXXXDX