Danfoss FC-102 Series AC Inverter for 1.1kW (1.5HP) 400V 3 Phase Fan or Centrifugal Pump in VxF control to 3A. Converts fixed frequency three phase 400V input to variable frequency three phase 400V to control the speed of a standard AC Induction Motor.
IP66/Type 4X rated for indoor or outdoor use including rooftop air handling units. Corrosion resistance complies with IEC 60721-3-3 level 3C3. For outdoor installations the Inverter must be installed under a suitable cover to protect it from direct exposure to sun, snow and ice.
Size A5: 242mm Wide x 200mm Deep x 420mm High.
Weight: 14kg (approx.)
Overload: 110% x 60 seconds, 135% x 0.5 seconds.
Speed Control Range: 0-590Hz
Braking: None.
No operator keypad included, 2 Analogue Inputs, 4 Digital Inputs, 1 Analogue Output, 2 Digital Input/Outputs, 2 Relay Contact sets, DC Bus +/- Terminals, Terminals for RS485 Communications.
FC Protocol, N2 Metasys, FLN Apogee communication protocols built-in as standard.
Programmable from a PC via USB and free Danfoss MCT 10 software.
Input Current: 2.7A
Input Voltage: 380-480V Three Phase ±10% at 50-60Hz ±5%
EMC Compliance: IEC EN55011 Second Environment Class C2 (Industrial). For First Environment Compliance (C1) Motor Cables are limited to 10m. Filter can be disabled if required.
Wall mount in clean environment or cubicle mount.
Rated 50°C Ambient.
Ventilation space in front: [not specified], above and below: 100mm, at sides: 0mm.
Heat Loss at max output: 58W
Mounting via 4 x holes at rear on 215mm x 402mm centres.
Manufacturer type code is FC-102P1K1T4E66H3XXXXOXSXXXXAXBXCXXXXDX.
Download the Danfoss FC102 Manual from the links below:-