Danfoss FC-102 Series AC Inverter for 2.2kW (3HP) 400V 3 Phase Fan or Centrifugal Pump in VxF control to 5.6A. Converts fixed frequency three phase 400V input to variable frequency three phase 400V to control the speed of a standard AC Induction Motor.
Dimensions: Size A4 200mm Wide x 175mm Deep x 390mm High.
Enclosure rating: IP55.
Weight: 9.7kg.
Overload: 110% x 60 seconds, 135% x 0.5 seconds.
Speed Control Range: 0-590Hz
Braking: None.
Features: Graphical Keypad, 2 Analogue Inputs, 4 Digital Inputs, 1 Analogue Output, 2 Digital Input/Outputs, 2 Relay Contact sets, DC Bus +/- Terminals, Terminals for RS485 Communications.
FC Protocol, N2 Metasys, FLN Apogee communication protocols built-in as standard.
Programmable from a PC via USB and free Danfoss MCT 10 software.
Input Current: 5A
Input Voltage: 380-480V Three Phase ±10% at 50-60Hz ±5%
EMC Compliance: IEC EN55011 First Environment Class C1 (Domestic and Industrial). Motor Cables are limited to 10m for C1 compliance. Filter can be disabled if required.
Mounting: Wall mount in clean environment or cubicle mount via 4 x holes at rear on 171mm x 401 centres.
Ambient: Rated 45°C.
Ventilation space in front: [not specified], above and below: 100mm, at sides: 0mm.
Heat Loss at max output: 88W
Manufacturers part number: 131U0964.
Full Type code: FC-102P2K2T4Z55H3XGXXOXSXXXXAXBXCXXXXDX.
Download the Danfoss FC102 Manual from the links below:-