Danfoss VLT FC-302 series AC Frequency Inverter for 15kW (20HP)in High Overload or 18.5kW (25HP) in Pump/Fan mode. 400V three phase motor in VxF control or Sensorless Flux control to 32A/ 37.5A. Converts fixed frequency three phase 400V input to variable frequency three phase 400V to control the speed of a standard AC Induction motor or permanent magnet synchronous motor.
Frame Size B3: 399mm high x 165mm wide x 249mm deep. IP20.
Weight: 12kg
Continuos Output Current: 32A (High Overload), 37.5A (Normal OVerload)
High Overload: 160% for 60 seconds every 10 minutes. Normal Overload: 110% for 0.5 seconds every 10 minutes.
Speed Control Range: 0 - 590Hz in VxF Control, 0 - 300 Hz in Sensorless Flux Control.
Braking: to minimum 28 ohm external resistor (not included) rated at 1400W continuous. See linked products below for compatible resistor. (Requires 2 resistors in parallel)
Graphical Keypad, 2 Analogue Inputs, 4 Digital Inputs, 1 Analogue Output, 2 Digital Input/Outputs, 2 Programmable Relay Outputs, Terminals for RS485 Communications.
1 x Safe Torque Off Input, Catagory 3 to SIL2, SILCL2, performance level "d".
Programmable from a PC via USB and free Danfoss MCT 10 software (see download link below).
Input Voltage: 380-500V Three Phase ±10% at 50-60Hz ±5%. Input Current 29A (High OVerload), 24A (Normal Overload).
EMC Compliant to Class A2 (C3) Industrial Environment.
Cubicle mount.
Ventilation space above and below should be 200mm.
Heat Loss is 379W/ 465W at full load.
Rated at 45°C Ambient. See Design guide for de-ratings for higher temperatures.
Part number: 131F9966.
Type Code is: FC302P15KT5E20H2BGXXXXSXXXAXBXCXXXDX.