Danfoss FC-102 Series AC Inverter for 2.2kW (3HP) 400V 3 Phase Fan or Centrifugal Pump in VxF control to 3A. Converts fixed frequency three phase 400V input to variable frequency three phase 400V to control the speed of a standard AC Induction Motor.
Size A5: 242mm Wide x 200mm Deep x 420mm High. IP55.
Weight: 13.5kg.
Overload: 110% x 60 seconds, 135% x 0.5 seconds.
Speed Control Range: 0-590Hz
Braking: None.
No Keypad
2 Analogue Inputs, 4 Digital Inputs, 1 Analogue Output, 2 Digital Input/Outputs, 2 Relay Contact sets, DC Bus +/- Terminals, Terminals for RS485 Communications.
FC Protocol, N2 Metasys, FLN Apogee communication protocols built-in as standard.
Programmable from a PC via USB and free Danfoss MCT 10 software.
Input Voltage: 380-480V Three Phase ±10% at 50-60Hz ±5%.
Continuous Input Current (380-440V): 5A.
Continuous Input Current (441-480V): 4.3A.
EMC Compliance: IEC EN55011 First Environment Class C1 (Domestic Environment) RFI Class A1/B.
Continuous Output Current (380-440V): 5.6A.
Continuous Output Current (441-480V): 4.8A.
Wall mount in clean environment or cubicle mount.
Rated 45°C Ambient.
Ventilation space in front: [not specified], above and below: 100mm, at sides: 0mm.
Heat Loss at max output: 88W.
Manufacturer part number is 131B7834.
Full Type code is FC-102P2K2T4E55H3XGX1XXSXXXXAXBXCXXXXDX.