Danfoss FC 102 HVAC IP20 3kW 400V 3ph AC Inverter Drive, HMI, C3 EMC

131B7393 (FC-102P3K0T4E20H3BGXXXXSXXXXAXBXCXXXXDX)

Order Code: 38995
Available to Order
Delivery normally 2 weeks
£688.00
(excl. VAT)
£825.60
(inc. VAT )
Price break
per unit
1+
£688.00

Condition: New with Warranty
Brand: Danfoss, Range: VLT HVAC FC 102

Danfoss FC-102 Series AC Inverter for 3kW (4HP) 400V 3 Phase Fan or Centrifugal Pump in VxF control to 7.2A. Converts fixed frequency three phase 400V input to variable frequency three phase 400V to control the speed of a standard AC Induction Motor.

Size A2: 90mm Wide x 205mm Deep x 268mm High. IP20.
Weight: 4.9kg.

Overload: 110% x 60 seconds, 135% x 0.5 seconds.
Speed Control Range: 0-590Hz
Braking: Fitted.

Graphical Keypad, 2 Analogue Inputs, 4 Digital Inputs, 1 Analogue Output, 2 Digital Input/Outputs, 2 Relay Contact sets, DC Bus +/- Terminals, Terminals for RS485 Communications.
FC Protocol, N2 Metasys, FLN Apogee communication protocols built-in as standard.
Programmable from a PC via USB and free Danfoss MCT 10 software.
Input Voltage: 380-480V Three Phase ±10% at 50-60Hz ±5%
Input Current: (380-440V): 6.5A
Input Current: (441-480V): 5.7A
EMC Compliance: IEC EN55011 Second Environment Class C3 (Industrial). Can be disabled if required.

Output Current (380-440V): 7.2A
Output Current (441-480V): 6.3A

Wall mount in clean environment or cubicle mount.
Rated 45°C Ambient.
Ventilation space in front: [not specified], above and below: 100mm, at sides: 0mm.
Heat Loss at max output: 116W
Mounting via 4 x holes at rear on 70mm x 257mm centres.

Manufacturer part number is 131B7393.
Full Type code is FC-102P3K0T4E20H3BGXXXXSXXXXAXBXCXXXXDX.

Download the Danfoss FC102 Manual from the links below:-