ABB Drives ACS355 IP66 Sensorless Flux Vector AC Frequency Inverter for 1.5kW (2HP) 400V 3 Ph motor in VxF or Vector control to 4.1A. Simple to set-up for a standard AC Induction motor.
IP66 / UL Type 4X protection for the harshest and most demanding of conditions. See linked products below for compatible options and standard (IP20) equivalent.
R1 Size - 195mm Wide x 281mm Deep x 305mm high. IP66 case.
Overload - 150% x 60seconds.
Speed Control Range - 0/500Hz.
Braking at full load for 27 seconds every 120 seconds to 130 Ohm minimum, 300 Ohm Maximum external resistor (not supplied) - see the Resistor options linked below or use the 'Which Resistor' button on this page.
Features - Assistant Operator Panel (Advanced Keypad), 2 x Analogue Inputs, 5 x Digital Inputs, 1 x Analogue Output, 1 x Digital Output, 1 x Relay Contact set.
DC Bus terminals with charge limit in circuit for DC supply or common bus energy saving applications.
'Safe Torque Off' function to SIL 3.
Programmable from a PC via 'DriveWindow' or using the ABB FlashDrop tool.EMC Filters to EN61800-3 to the 2nd Environment (Industrial).
Input Current - 6.9A.
Input Voltage - 380-480V three phase at 48-63Hz.
EMC Filters to EN61800-3 to the 2nd Environment (Industrial).
Rated at 40C Ambient.
Ventilation space above and below - 75mm.
Ventilation space at sides - Ensure that there is enough free space around the drive to clean it.
Heat Loss at max output - 68.7W.
Wall Mounting using 4 x screw fixings at rear. Use spacers and fastening lugs to provide clearance for cleaning.
Full part number is - ACS355-03E-04A1-4+B063 (3AUA0000058160) and is a direct replacement for the equivalent ACS350.
Download the ABB ACS355 Manual and IP66 Supplement from the links below:-