ABB ACH580 series AC Inverter for a 4kW (5HP) 400V 3 Ph motor to 9.4A
Size R1: 125mm Wide x 233mm Deep x 330mm High (glandbox is integrated). IP55.
Weight: 5.5kg.
Overload: 150% x 60 seconds every 10 minutes (High Overload)
Overload: 110% x 60 seconds every 10 minutes
Speed Control Range: 0-500Hz.
Braking: To 52 Ohm minimum, 140 Ohm maximum external resistor to 3.9kW (not supplied) - See the Resistor options linked below or use the 'Which Resistor' button on this page.
Supplied with Advanced Operator Keypad (Assistant Control Panel)
2 Analogue Inputs, 6 Digital Inputs, 2 Analogue Outputs, 3 Relay Contact Sets, terminals for RS-485/Modbus RTU communications, terminals for dual channel SIL3 safe torque off (STO), 24V AC/DC input to power the control unit when the main supply is disconnected.
Input Current: [as output current]
Input Voltage: 380-480V Three Phase +10% -15% at 50-60Hz ±5%
EMC Compliance: IEC EN61800-3:2004 + A1:2012 Category C2 (Industrial or restricted Domestic)
Rated 40°C Ambient.
Ventilation space above: 30mm, below: 200mm, at sides: 150mm, in front: [Not Specified]
Heat Loss at max output: 133W
Mounting via 4 x 6.5mm diameter slotted holes at rear on 98mm x 317mm centres.
Manufacturers Part Number: ACH580-01-09A4-4+B056 (3AUA0000083591). Replaces ACH550-01-08A8-4+B055.