SSD 690P AC Frequency Inverter for 180kW (250HP) 400V 3 Ph motor to 361A at high overload (Heavy Duty) or 220kW (300HP) to 420A when normal duty (Fan/Pump rated), operates in VxF, Sensorless Flux Vector or Full Closed Loop Flux Vector control (when the optional encoder board is fitted).
Requires external input line choke - part number CO389936U402 (not included - see linked products below)
Size G - 455mm Wide x 465mm Deep x 1384mm High (includes length of exhaust duct). Space is required at sides for bars and above for roof mounting fan.
Weight - 108kg
Overload - 150% x 60 seconds and 180% for 0.5seconds at high overload rating or 110% for 10 seconds for normal duty (fan/pump rating).
Switching frequency - 2.5kHz at full output, reducing to 1.2kHz at maximum overload.
Speed Control Range - 0/250Hz at continuous rating, or 120Hz if used to maximum overload.
Braking - 100% for 20 seconds or 35% Continuous to 2.08 Ohm external resistor - See the Resistor options linked below or use the 'Which Resistor' button on this page.
4 x Analogue Inputs, 8 Digital Inputs, 3 Analogue outputs, 3 Digital outputs (relay contacts).
Input Current - 336A at high overload or 402A when Fan/Pump rating set.
Input Voltage - 380/460V three phase +-10% at 50/60Hz.
Input fuse - 400A at high overload or 450A when Fan/Pump rating set - to suit input bridge at 813000A²s
Cubicle mounting.
Rated at 40C Ambient.
Ventilation fan requires a separate 115V supply fused at 3A.
Heat Loss at max output - 3723W at high overload and 4409W when Fan/Pump rating set.
Full part number is - 690-433361G1-B00P00-A400 (was - 690PG-1800-400-0011-UK-0-0-0-0-B0-115-0). - Exactly the same as SSD Drives and Eurotherm Drives - 690PG-1800-400-0011-UK-0-0-0-0-B0-115-0.
The menu uses simple to understand English-language terms to describe its selection and functions.
Download the 690P Technical and Software Manual from the links below:-