Danfoss VLT FC-302 series AC Frequency Inverter for 1.5kW (2HP) 400V three phase motor in VxF control or Sensorless Flux control to 4.1A. Converts fixed frequency three phase 400V input to variable frequency three phase 400V to control the speed of a standard AC Induction motor or permanent magnet synchronous motor.
Frame Size A2: 268mm high x 90mm wide x 205mm deep. IP20.
Weight: 4.9kg
Overload: 160% for 60 seconds.
Speed Control Range: 0 - 590Hz in VxF Control, 0 - 300 Hz in Sensorless Flux Control.
Braking: to minimum 270 ohm external resistor (not included) 200W continuous. See linked products below for compatible resistor.
Graphical Keypad, 2 Analogue Inputs, 4 Digital Inputs, 1 Analogue Output, 2 Digital Input/Outputs, 2 Programmable Relay Outputs, Terminals for RS485 Communications.
1 x Safe Torque Off Input, Catagory 3 to SIL2, SILCL2, performance level "d".
Programmable from a PC via USB and free Danfoss MCT 10 software (see download link below).
OPTION A: PROFIBUS Converter MCA114
OPTION D: MCB-107 24V DC backup
Input Voltage: 380-500V Three Phase ±10% at 50-60Hz ±5%. Input Current 3.7A.
EMC Compliant to Class A1/B (C1/C2) Domestic Environment.
Cubicle mount.
Ventilation space above and below should be 100mm.
Heat Loss is 62W at full load.
Rated at 45°C Ambient. See Design guide for de-ratings for higher temperatures.
Part number: 131U7749
Type Code is: FC-302P1K5T5E20H1BGCXXXSXXXXAUBXCXXXXD0