Delta ME300 Basic Compact Series AC Inverter for 1.5kW (2HP) 230V 3ph motor to 7,5A at high overload or 1.5kW (2HP) to 8,5A when Fan/Pump rated. Operates in VxF or Sensorless Vector and converts fixed frequency Single Phase 230V input to variable frequency Three Phase 230V to control a standard AC induction, permanent magnet motor, IPM (Interior permanent magnet) and SPM (surface mounted permanent magnet).

Input Current: 15,8A at High Overload, 17,9A when Fan/Pump rated.
Input Voltage: Single phase AC 200–240 V (-15– +10%), 50/60 Hz.
EMC Compliance: IEC EN 61800-5-1 Category C2 @ 20m (Industrial). Disabled by default, can be enabled via screw.

Frame Size: C2 87mm Wide x 163mm Deep x 157mm High. IP20.
Mounting via 4 x M5 bolts (not supplied) at rear on 73mm x 144.5mm centres. (Optional DIN-Rail mounting available - see linked products below).
Weight: 1.5kg.

Overload:
150% for 60 seconds. High Overload. (Heavy Duty, HD), 200% of rated output current for 3 seconds.
120% for 60 seconds. Fan/Pump Rated. (Normal Duty, ND), 150% of rated output current for 3 seconds.

Speed Control Range: 0-599Hz. +/- 0.1%.
1 : 50 (V/f, SVC control for IM, heavy duty).
1 : 20 (SVC control for PM, heavy duty).
Switching (Carrier frequency): 2-15 kHz.

Braking (DBr): Built-in braking transistor for 125% Torque x 10 seconds every 100 seconds to 47.5 Ohm minimum external resistor (not supplied). Recommended resistor 91 Ohms 200W - see the Resistor options linked below or use the 'Which Resistor' button on this page. (Does not have to be used; available if required)

Product Features: Integrated Operator Keypad with integral potentiometer, (Option external keypad can be connected to the RS485 port (RJ45)) - see linked products below.
1 Analogue Input (0-10Vdc, 0-20mA & 4-20mA), 5 Programmable Digital Inputs (PNP/NPN), 1 Pulse Input (10kHz), 1 Analogue Output, 1 Digital Output,Modbus RS485 (RJ45)
1 Relay set of Changeover contacts (Resistive Load 3A/250VAC -5A/30VDC,  Inductive Load 1.2A/250VAC -2A/30VDC)
Common DC Bus Terminals

Safe Torque Off (STO): Functional to SIL2 (EN61800), EN 60204-1 Category 0, EN 62061 SIL CL 2, SO 13849-1:2015 Category 3 PL d.

​Environment and installation:
Pollution degree 2, Indoor use only, Cubicle mount only.
Rated at IP20

Humidity: 90%
Altitude: 0 ~ 1000m for normal operation
Heat Loss at High Overload: 77.5W total at max output

Cooling: Fan cooling.
Ambient operating temperature to 50°C (40°C when units mounted side-by-side)
Ventilation space in front [not specified], above: 50mm, below: 50mm, at sides 30mm.

Certification: CE, UL, RoHS RCM, TUV, REACH, KC.

Manufacturer part number is VFD7A5ME21AFSAA

Download the Delta ME 300 manuals and datasheets from the link below:

You may also be interested in...

Photo of Dynamic Brake Resistor, 56 Ohms, 200 Watts

Dynamic Brake Resistor, 56 Ohms, 200 Watts

IRV 200 56R J

(CZ463068)

Order code: 19536

10+ in stock

£58.00
£55.10
£52.20
1+
10+
50+
£4.00
1+
Photo of Mersen 32A 690Vac 10mm x 38mm gR High Speed Fuse

Mersen 32A 690Vac 10mm x 38mm gR High Speed Fuse

H1014583

(FR10GR69V32)

Order code: 22318

25+ in stock

£5.00
1+