A drive from our stock was supplied on a same day delivery for a Technogym Run 600 XP Treadmill. The original Hitachi SJ100-015NFE had failed, after providing excellent service and was replaced by Dean Wright of Telford.
The replacement drive was an ACS150 rated at 1.5kW. This is a general purpose Inverter Drive, used for many applications including; small machine tools, conveyers, energy saving fans and pumps, small hoists, turntables, food processing machines and many other applications in all areas of Industry.
The Hitachi Inverter has a number of settings changed from the default values. They are as follows:-
Parameter |
Desc |
Value |
F6 |
Ramp up time |
set to 15 seconds |
F7 |
Ramp down time |
set to 15 seconds |
A0 |
starting torque |
Set to 2 for high |
A1 |
motor rating in kW |
Set to 1 |
A26 |
|
Set to 1.5 so the drive turns off when the setpoint is below 1.5Hz |
A27 |
max speed for the setpoint |
Set to 97 |
A42 |
disable reverse rotation |
Set to 0 |
A48 |
0/10V analogue input |
Set to 1 |
A63 |
Max frequency |
Set to 98 |
C0 |
external trip function on one of the terminals |
Set to 09 |
C20 |
relay contact function (Fault or Healthy?) |
set to 01 |
If you know what the equavalent ACS150 settings are, let us know and we will add your information.