Your Cart is empty!
Condition: New with Warranty Brand: Siemens, Range: SINAMICS Accessories
Three Phase AC Line Choke for 850A DC Thyristor Drive input.
DC Drive Rating or Armature Current: 850A Rated AC Line Current: 706A AC continuous. Ensure the combined AC Current for the Armature and Field Current does not exceed the continuous rating (AC Current for the Armature is 0.82 x the DC Current). Inductance: 0.042mH Input Voltage: 400V three phase +15% -20% at 50/60Hz. Rated at 40°C Ambient. Heat Loss: 424.8W
Enclosure: IP00
Connections: Ready Drilled Bars. Dimensions: 454mm x 165mm Base (247mm deep) x 378mm high overall (requires additional space above and in front for Customers connections). Fixings: Slots for M12 bolts at 425mm x 125mm. Weight: 81.6kg
Part number: 6RX1800-4DK11 Manufactured in Austria
Download the Drawing and Product Manual from the links below:-
6RA8087-6DS22-0AA0
Order code: 28961
Delivery 8 weeks
6RA8087-6DV62-0AA0
Order code: 28982
We've sent you a message containing a confirmation link. Click the link to complete the process.