Yaskawa GA500 Series AC Inverter for 4kW (5HP) 400V 3ph motor to 9.2A at high overload or 5.5kW (7.5HP) to 11.9A when Fan/Pump rated. Operates in VxF or Sensorless Vector and converts fixed frequency Three Phase 400V input to variable frequency Three Phase 400V to control a standard AC induction, permanent magnet or synchronous reluctance motor.
Size 3c: 140mm Wide x 193mm Deep x 128mm High. IP20.
Weight: 2.6kg.
4kW; 9.2A with 150% overload for 60 seconds. - Heavy Duty (HD). (Once every 10 minutes) - Default Setting
5.5kW; 11.9A with 110% overload for 60 seconds. Normal Duty (ND). (Once every 10 minutes) - Change paramenter C6-01 to 1 for ND Rating
Speed Control Range: 0-590Hz.
Braking (DBr): Built-in braking transistor for 100% Torque for 10 seconds every 100 seconds (10% duty cycle). A 100 Ohm minimum external resistor is required for Dynamic Braking. Resistor is not supplied and should only be fitted if this feature is required.
Includes removable Operator Keypad, 2 Analogue Inputs, 7 Digital Inputs, 1 Pulse Input, 1 Analogue Outputs, 1 Pulse Output, 2 Digital Outputs, 1 Relay Output, USB mini-B port for PC connection.
Serial Communications: Terminals for MEMOBUS/Modbus RS485 (Wired)
Safe Torque Off (STO) function to SIL3 (EN61800-5-2)
24V DC input to power the control unit when the main supply is disconnected. (24V, 700mA nominal)
Input Current: 10.4A at High Overload, 14A when Fan/Pump rated.
Input Voltage: 380-480V Three Phase -15% +10% at 50-60Hz ±5%.
EMC Compliance: IEC EN 61800-3 Category C2 (Restricted Domestic). Disabled by default, can be enabled via screw.
Cubicle mount.
Rated at 40°C ambient.
Ventilation space in front: [not specified], above: 100mm, below: 100mm, at sides: 30mm.
Heat Loss at High Overload: 89W total at max output, split 29W from the Electronics and 60W from the heatsink, when through panel mounted (see options linked below).
Heat Loss at Fan/Pump Rating: 124W total at max output, split 41W from the Electronics and 83W from the heatsink, when through panel mounted (see options linked below).
Mounting via 4 x M bolts (not supplied) at rear on 118mm x 128mm centres.
Manufacturer part number is CIPR-GA50C4012EBAA
Replaces: CIMR-VC4A0011BAA (VZA4-4P0-BAA)