Parker SSD 890 Series AC Frequency Inverter for 18.5kW 400V 3 Ph motor to 39A or 25HP 500V 3ph motor to 35A. Suitable for a Standard AC Induction Motor in VxF, Sensorless Vector Control or Full Closed Loop Vector Control with an optional Speed Feedback Card. Also suitable to control a PM Brushless AC Servo Motor when fitted with an optional Feedback Card. (See Feedback Options below)
Size D - 160mm Wide x 258.5mm Deep x 433.6mm High. IP20
Weight: 12.1kg.
Overload - 150% x 60 seconds
Speed Control Range: 0-1000Hz (VxF), 0-350Hz (Closed-loop Vector), 0-120Hz (Sensorless Vector).
Braking (DBr) - To 20 Ohm minimum external resistor (not supplied) - See the Resistor options linked below or use the 'Which Resistor' button on this page.
Safe Torque Off (STO) to SIL3 or PLe level as per EN ISO13849 and EN61800-5-2.
4 Analogue Inputs, 7 Digital Inputs, 2 Analogue Outputs, 2 Digital Inputs/Outputs, 1 Relay Contact Set, USB port for Programming.
Input Current - 42A.
Input Voltage - 380 - 500Vac ±10% at 50/60Hz
EMC Compliance: IEC EN 61800-3 Category C3 (Industrial)
Wall mount in clean environment or cubicle mount.
Rated 40°C Ambient.
Ventilation space in front - [Not Specified]
Ventilation space above and below - 150mm.
Ventilation space at sides - 0mm (drives can be mounted side by side).
Mounting via 3 x holes at rear (3 top, 3 bottom) on 37.5mm x 413.6mm centres.
Mounting onto 35mm DIN rail using included fitting kit.
Option Modules were originally supplied fitted to the 890SD, Modules are now supplied as additional items (Please see linked items below).
Additional option cards are required to achieve the variants given below:
Part Number Variation in block 4 (Legacy Part Variations in blocks 10): 1(E1), 3(EQ), 5(RE), 6(RR), 7(M1), L(LS) eg 890SD-531200B0-B00-1A300 (890SD/5/0002B/B/00/A/UK/00/00/EQ/00/00) was supplied with an Encoder Feedback Option card 8902-EQ-00 fitted.
Part Number Variation in block 4 (Legacy Part Variations in block 11): N(CB), C(CN), D(DN), H(IP), T(IM), P(PB), 7(M1), S(RS), K(CT), E(EP) eg 890SD-531200B0-B00-1A0P0 (890SD/5/0002B/B/00/A/UK/00/00/00/PB/00) was supplied with Profibus Communications Card 8903-PB-00 fitted
Full part number is - 890SD-532390D0-B00-1A000. Was 890SD/5/0039D/B/00/A/UK/00/00/00/00/00.
Download the Parker 890SD Manual and Programming Guide from the links below:-