Parker AC30P AC Frequency Inverter for 0.75kW (1HP) 400V 3 Ph motor to 2.5A at high overload or 1.1kW (1.5HP) to 3.5A when Fan/Pump rated, operates in VxF, Sensorless Flux Vector or Full Closed Loop Flux Vector control (when the optional encoder board is fitted). Simple set-up and ready to run in VxF from its default settings.
Size D- 100mm Wide x 255mm Deep x 286mm High overall. IP20
Weight: 4.5kg
Overload - 150% x 60 seconds and 180% for 3.0seconds.
Speed Control Range - 0/500Hz (default), 0/1000Hz or 0/1500Hz
Switching Frequency 4 to 16kHz.(Derating may apply)
Braking (DBr) - Maximum of 20 seconds at maximum current @ a duty 30% into minimum 520 Ohm external resistor - See the Resistor options linked below or use the 'Which Resistor' button on this page
Brake Switch Peak Current 1.5A (20s, 30% Duty) Continuous current 1A at 0.75kW
Graphical Keypad (HMI)
2 x Analogue Inputs, 3 Digital Inputs,4 Programmable Digital I/O, 2 Analogue outputs, 2 Digital outputs (relay contacts), 2 Ethernet Ports.
Ethernet IP/ ProfiNET available with firmware upgrade.
Input Current –2.8A at high overload or 4A when Fan/Pump rating set.
Input Voltage - 380/480V three phase +-10% at 50/60Hz.
Input fuse - 10A when Fan/Pump rating set
Filters: EMC Compliance: No Filter, External filters can be fitted.
Standard 3C3 coated PCBs
Safety Features: STO & Safe Stop (SS1)
Wall mount in clean environment or cubicle mount.
Rated at 40C Ambient
Ventilation space Front - 10mm
Ventilation space above and below - 75mm.
Ventilation space at sides - 0mm.
Heat Loss at max output - 55W (estimated efficiency 95%)
Mounting –M4screw fixings on 80mm x 270mm centres.
Manufacturer Part Number is 31P-4D0004-BE-2S-0000.
The AC30 Technical Product Manual can be downloaded from the link below:-