ABB ACS580 series AC Inverter for 55kW (75HP) 400V 3 Ph motor to 105A at high overload or 75kW (100HP) to 138A when Fan/Pump rated. Operates in VxF or Sensorless Vector control and converts fixed frequency Three Phase 400V input to variable frequency 400V to control the speed of a standard AC induction motor.
Size R6: 252mm Wide x 369mm Deep x 548mm High (height is 727mm when glandbox fitted). IP55.
Weight: 45kg.
Overload: 150% x 60 seconds every 10 minutes (High Overload)
Overload: 110% x 60 seconds every 10 minutes (Fan/Pump rated)
Speed Control Range: 0-500Hz.
Braking: None (external braking unit optional)
Supplied with Operator Keypad (Assistant Control Panel)
2 Analogue Inputs, 6 Digital Inputs, 2 Analogue Outputs, 3 Relay Contact Sets, terminals for RS-485/Modbus RTU communications, terminals for dual channel SIL3 safe torque off (STO), 24V AC/DC input to power the control unit when the main supply is disconnected.
Input Current: [as output current]
Input Voltage: 380-480V Three Phase +10% -15% at 50-60Hz ±5%
EMC Compliance: IEC EN61800-3:2004 + A1:2012 Category C2 (Industrial or restricted Domestic)
Cubicle mount.
Rated 40°C Ambient.
Ventilation space above: 155mm, below: 300mm (incl. glandbox), at sides: 150mm, in front: [Not Specified]
Heat Loss at max output: 1476W
Mounting via 6 x M8 bolts at rear on 213mm x 531mm and 571mm centres.
Manufacturer Part Number is ACS580-01-145A-4+B056 or 3AUA0000083579.
Download the ABB ACS580-01 Manual and Quick Start Guide from the links below:-