ABB ACS580 series AC Inverter for 11kW (15HP) 400V 3 Ph motor to 24.6A at high overload or 15kW (20HP) to 30.4A when Fan/Pump rated. Operates in VxF or Sensorless Vector control and converts fixed frequency Three Phase 400V input to variable frequency 400V to control the speed of a standard AC induction motor.
Size R3: 206mm Wide x 237mm Deep x 490mm High (glandbox is integrated). IP55.
Weight: 14.9kg.
Overload: 150% x 60 seconds every 10 minutes (High Overload)
Overload: 110% x 60 seconds every 10 minutes (Fan/Pump rated)
Speed Control Range: 0-500Hz.
Braking: To 16 Ohm minimum, 37 Ohm maximum external resistor to 15kW (not supplied) - See the Resistor options linked below or use the 'Which Resistor' button on this page.
Supplied with Operator Keypad (Assistant Control Panel)
2 Analogue Inputs, 6 Digital Inputs, 2 Analogue Outputs, 3 Relay Contact Sets, terminals for RS-485/Modbus RTU communications, terminals for dual channel SIL3 safe torque off (STO), 24V AC/DC input to power the control unit when the main supply is disconnected.
Input Current: [as output current]
Input Voltage: 380-480V Three Phase +10% -15% at 50-60Hz ±5%
EMC Compliance: IEC EN61800-3:2004 + A1:2012 Category C2 (Industrial or restricted Domestic).
Cubicle mount.
Rated 40°C Ambient.
Ventilation space above: 53mm, below: 200mm, at sides: 150mm, in front: [Not Specified]
Heat Loss at max output: 492W
Mounting via 4 x 7.2mm diameter slotted holes at rear on 160mm x 473mm centres.
New Part Number is ACS580-01-033A-4+B056 or 3AXD50000038978.
Download the ABB ACS580-01 Manual and Quick Start Guide from the links below:-