ABB ACH580 HVAC series AC Inverter for 22kW (30HP) 400V 3 Ph motor to 42.8A when Fan/Pump rated. Operates in VxF or Sensorless Vector control and converts fixed frequency Three Phase 400V input to variable frequency 400V to control the speed of a standard AC induction motor, permanent magnet synchronous motor or synchronous reluctance motor.
Output Current: 42.8A
Peak Output Current: 67.9A for 2 seconds at startup.
Overload: 110% x 60 seconds every 10 minutes.
Size R3: 206mm Wide x 237mm Deep x 490mm High.
IP Rating: IP55.
Weight: 13kg
Speed Control Range: 0 to 500Hz.
Braking (DBr): Internal Brake Switch Fitted; External braking resistor (not supplied) to minimum 10 Ohms, maximum 25kW - see linked products below for compatible option.
Keypad (HMI): Removable Assistant Control Panel ACH-AP-H included - multi-lingual with multi-line LCD Display.
2 x Analogue Inputs, 2 x Analogue Outputs, 6 x Digital Inputs, 3 x Relay Contact sets.
Fieldbus: BACnet MS/TP, Modbus RTU and N2. (Twin wire)
Safe Torque Off: Terminals for dual channel SIL3/PLe STO. (Linked out as default)
Input Current: 45A.
Input Voltage: 380 to 480V three phase +-10% at 50/60Hz.
Input Fuse: 63A. gG (IEC) fuse can be used if operation time is less than 0.5s. See manual for uR or aR alternatives.
Built in choke to minimise supply harmonics.
EMC Compliance: to EN61800-3 1st Environment, C2 (Industrial and restricted domestic)
Wall Mount.
Rated Ambient: 40℃.
Ventilation Space: Above: 200mm, Below: 53mm, Sides: 150mm, Front: Not Given
Heat Loss at max output: 619W.
Mounting: via 4 x slotted holes at rear for M6 screws on 473mm x 160mm centres.
Full part number: ACH580-01-046A-4+B056
Previous part number: ACH580-01-045A-4+B056. Same rating but dimensions are different.
Please note ACH550 to ACH580 ratings do not necessarily match. This listing is rated at or above the Output Current of the previous generation ACH 550-01-038A+B055
Download the ACH580 Manuals from the links below:-