ABB ACH580 HVAC series AC Inverter for 1.1kW (1.5HP) 400V 3 Ph motor to 3.1A when Fan/Pump rated. Operates in VxF or Sensorless Vector control and converts fixed frequency Three Phase 400V input to variable frequency 400V to control the speed of a standard AC induction motor, permanent magnet synchronous motor or synchronous reluctance motor.
Output Current: 3.1A
Peak Output Current: 4.7A for 2 seconds at startup.
Overload: 110% x 60 seconds every 10 minutes.
Size R1: 128mm Wide x 233mm Deep x 403mm High.
IP Rating: IP55.
Weight: 4.8kg
Speed Control Range: 0 to 500Hz.
Braking (DBr): Internal Brake Switch Fitted; External braking resistor (not supplied) to minimum 52 Ohms, maximum 0.9kW - see linked products below for compatible option.
Keypad (HMI): Removable Assistant Control Panel ACH-AP-H included - multi-lingual with multi-line LCD Display.
2 x Analogue Inputs, 2 x Analogue Outputs, 6 x Digital Inputs, 3 x Relay Contact sets.
Fieldbus: BACnet MS/TP, Modbus RTU and N2. (Twin wire)
Safe Torque Off: Terminals for dual channel SIL3/PLe STO. (Linked out as default)
Input Current: 3.3A.
Input Voltage: 380 to 480V three phase +-10% at 50/60Hz.
Input Fuse: 6A. gG (IEC) fuse can be used if operation time is less than 0.5s. See manual for uR or aR alternatives.
Built in choke to minimise supply harmonics.
EMC Compliance: to EN61800-3 1st Environment, C2 (Industrial and restricted domestic)
Wall Mount.
Rated Ambient: 40℃.
Ventilation Space: Above: 137mm, Below: 116mm, Sides: 150mm, Front: Not Given
Heat Loss at max output: 55W.
Mounting: via 4 x slotted holes at rear for M5 screws on 317mm x 98mm centres.
Full part number: ACH580-01-03A4-4+B056
Previous part number: ACH580-01-03A3-4+B056
Please note ACH550 to ACH580 ratings do not necessarily match. This listing is rated at or above the Output Current of the previous generation ACH 550-01-03A3+B055