Condition: New with Warranty Brand: REO UK Ltd, Range: Input Choke
2% AC Line Choke to 90A Three Phase. Connect to the mains input of a 3ph AC Inverter Drive to increase protection from mains transients, reduce harmonic current (THD) and reduce the RMS load. Recommended for an Inverter Drive connection to a high fault level low impedance supply, where sliding contacts on busbars are present and where the incoming power supply is prone to spikes, dips notches or other disturbances.
Current Rating: 90A. Overload: 1.5 x for 60 seconds onece per hour. Voltage: up to 500V 3 phase Inductance: 0.16mH. Power Loss: 104W. Protection: IP00. Dimensions: 230mm x 125mm x 200mm High. Weight: 11kg. Standards: EN 60289 / EN 61558
Also known as: Mains Choke, Line Reactor, AC Choke, AC Inductor or Input Choke.
Part Number: NCNW905/90.
NCNW903/90
(201020903009500)
Order code: 38301
Delivery 3-5 days
CNW906/90
Order code: 31553
2 in stock
3+ normally 7 weeks