Your Cart is empty!
Condition: New with Warranty Brand: REO UK Ltd, Range: Input Choke
2% AC Line Choke to 36A Three Phase. Connect to the mains input of a 3ph AC Inverter Drive to increase protection from mains transients, reduce harmonic current (THD) and reduce the RMS load. Recommended for an Inverter Drive connection to a high fault level low impedance supply, where sliding contacts on busbars are present and where the incoming power supply is prone to spikes, dips notches or other disturbances.
Current Rating: 36A. Overload: 1.5 x for 60 seconds onece per hour. Voltage: up to 500V 3 phase Inductance: 0.4mH. Power Loss: 43W. Protection: IP00. Dimensions: 155mm x 76m x 170mm High. Weight: 4kg. Standards: EN 60289 / EN 61558
Also known as: Mains Choke, Line Reactor, AC Choke, AC Inductor or Input Choke.
Part Number: NCNW905/36
NCNW903/36
(201020903000500)
Order code: 38299