When power is removed from a Parker SSD 650 Series Inverter it will trip with a DC-LO alarm. This occurs a couple of seconds before it powers off. When power is restored this alarm will normally need to be reset before the drive will run again.
For some applications, this behavour may not be desirable. However, the appropriate safety considerations must be reviewed before enabling auto-start on power-up.
To auto-start on power-up access the SET : SETP menu and set the following parameters:-
Parameter |
Description |
Value |
ST23 |
Auto restart trigger |
0002 |
ST22 |
Auto restart delay |
1 |
ST21 |
Auto restart attempts |
Min 1, Max 10 |
This information was kindly provided by Simon Clarke of Parker SSD Drives Technical Support.