Motortronics Synergy Series Soft Starter suitable for starting standard three phase induction motors to 110kW (146HP) at 195A when connected inline or to 160kW (213HP) at 280A when connected inside Delta (both ratings are subject to application).
When connected inline; rated to suit motors and Trip Class Ratings:-
110kW, 195A at 400V – Trip Class 10 (Continuous)
90kW, 160A at 400V – Trip Class 20 (Continuous)
75kW, 132A at 400V – Trip Class 30 (Continuous)
When connected inside Delta; rated to suit motors and Trip Class Ratings:- Note Energy Saving is not available in this mode.
185kW, 338A at 400V – Trip Class 10 (Continuous)
150kW, 277A at 400V – Trip Class 20 (Continuous)
110kW, 229A at 400V – Trip Class 30 (Continuous)
(See Quick Start Guide and Trip Class Guide for guidance, also for UL current and HP ratings)
Size 2: 143mm Wide x 232mm Deep x 318mm High. IP00 (IP20/NEMA1 option - see linked products below).
Weight: 6.5kg.
Features include:
Integral keypad
1 Analogue Input + 1 Analogue Output @ 0-10V 10mA / 4-20mA
4 x programmable output relays (2 groups)
3 x programmable digital inputs (2 Groups @ 24Vdc or 110Vac or 230Vac +10% -15% voltage dependent voltage applied to D1-2 Com terminals)
USB terminal for data logging and parameter setting/saving.
Thermistor input (PTC).
Input Voltage: 200Vac to 480Vac, at 45-65Hz
Recommended fuses can be found in the Quick Start Guide
Aux supply options: Requires Single Phase 110V or 230V ac rms, or 24vdc
Cubicle mount.
Ventilation space above and below: 100mm
Ventilation space at sides: 40mm
Ventilation space in front: 25mm
Mounting via 4 bolts at rear on 80mm x 304mm centres.
Rated at 50 degrees C Ambient.
Manufacturer part number is VMX-SGY-205-4-01 (was Fairford SGY-205-4-01)
Download the Motortronics Synergy Manual from the links below:-