TECO Westinghouse 1.1kW 3ph 4 Pole High Efficiency Flange Mounting (B5) D90S Frame AC Motor for 230V or 400V 3 phase supply. Inverter Rated for use with a Variable Frequency Inverter Drive having 1ph or 3ph input and 3ph output, or a fixed frequency mains supply at 50Hz.
Fixed mains supply output: 1.1kW (1.5HP) x 1435RPM at 230V or 400V x 50Hz 3ph.
Inverter Supply Output: 15:1 Speed Control range from 144RPM to 2153RPM for 5Hz to 75Hz control, with suitable de-rating at the lower speeds.
Full Load Current: .2A at 230V, or 2.44A at 400V.
Power Factor: 0.8 when mains connected at 50Hz.
Efficiency: 81.4%
Dimensions: 176mm Wide x 343mm Long x 228mm high overall in its IP55 enclosure.
Mounting: Flange mount on 4 x 12mm holes equispaced on 165mm PCD with 130mm diameter spigot in the 200mm diameter flange.
Shaft: 24mm dia x 50mm with 8mm wide key.
Weight: 15kg.
Multi-mount design: The feet (if fitted) can be moved to allow the terminal box to be positioned at the top or on either side. The terminal box can also be repositioned to the rear of the motor if required. Vertical motor mounting is also possible with the shaft facing down.
Ambient.: Rated at 40C
Ventilation space required at rear cooling air intake.
Thermistor for over-temperature protection is included.
Part number: ALAA-0090S0-10004-IZ (I2-1.10-4B5)
For Variable Speed use:-
Part Time Output when Inverter powered is...
3.7Nm - 1.1kW (1.5HP) x 2870RPM at 100Hz
7.3Nm - 1.1kW (1.5HP) x 1435RPM at 50Hz
7.32Nm - 0.55kW (0.74HP) x 718RPM at 25Hz
3.66Nm - 0.11kW (0.08) x 144RPM at 5Hz
Continuous Output when Inverter powered is...
4.9Nm - 1.1kW (1.5HP) x 2153RPM at 75Hz
7.3Nm - 1.1kW (1.5HP) x 1435RPM at 50Hz
6.22Nm - 0.47kW (0.6HP) x 718RPM at 25Hz
3.66Nm - 0.06kW (0.08HP) x 144RPM at 5Hz
Download the full Manual and Dimensions from the link below:-
From Jan 1st 2017, three phase electric induction motors with a rated output of 0.75kW to 375kW and efficiency less than IE3 must be equipped with a variable speed drive (Inverter Drive). For exceptions, see EC Commission Regulation 640/2009.