TEC IE2 2.2kW Three Phase Motor 230V/400V 2 Pole 90L Frame B5 Anticon

TECA2-90L1-2-IE2-AntiCon-240V

Order Code: 35301
Obsolete Product
This item is now obsolete. Alternatives may be available - see linked products below.

Brand: TEC Electric Motors, Range: TECA Three Phase IE2 Aluminium

TEC Electric 2.2kW 3ph 2 Pole High Efficiency Flange Mounting (B5) 90L Frame Aluminium AC Motor for 230V or 400V 3 phase supply.  Inverter Rated for use with a Variable Frequency Inverter Drive having 1ph or 3ph input and 3ph output, or a fixed frequency mains supply at 50Hz.

Fitted with an a 240V AC anticon heater.

Fixed Mains Supply Output:  2.2kW (3HP).
Speed:  2860RPM.
Voltage:  230V or 400V x 50Hz 3ph.
Inverter Supply Output:  14:1 Speed Control range from 286RPM to 4004RPM for 5Hz to 70Hz control, with suitable de-rating at the lower speeds.

Full Load Current:  7.9A at 230V, or 4.5A at 400V.
Power Factor:  0.84 when mains connected at 50Hz.
Efficiency:  83.2%

Dimensions:  175mm Wide x 337mm Long x 229mm high overall.
Enclosure Rating:  IP55.
Flange mount on 12mm holes at 165mm PCD with 130mm diameter spigot in the 200mm diameter flange.
Shaft:  24mm dia x 50mm with 8mm wide key.
Weight:  17.5kg.

Ambient:  Rated at 40C.
Ventilation space required at rear cooling air intake.
Thermistors included for external over-temperature protection device.
Part number:  TECA2-90L1-2-B5-Anticon

For Variable Speed use:-
Part Time Output when Inverter powered is...
5.25Nm - 2.2kW ( 2.95HP) x 4004 RPM at 70 Hz
7.35Nm - 2.2kW ( 2.95HP) x 2860 RPM at 50 Hz
7.35Nm -1.1kW ( 1.47HP) x 1430 RPM at 25 Hz
7.35Nm - 0.22kW ( 0.29HP) x 286 RPM at 5 Hz
Continuous Output when Inverter powered is...
5.25Nm - 2.2kW ( 2.95HP) x 4004 RPM at 70 Hz
7.35Nm - 2.2kW ( 2.95HP) x 2860 RPM at 50 Hz
6.24Nm - 0.94kW ( 1.25HP) x 1430 RPM at 25 Hz
3.67Nm - 0.11kW ( 0.15HP) x 286 RPM at 5 Hz

Extended Warranty Available: When a TEC AC Motor is used with a TECDrive AC Inverter (see linked products below) the warranty period is 2 years (from dispatch). Standard warranty is 1 year.
For the extended warranty to be valid the TEC AC Inverter and TEC Motor must be on the same order and used together when on site.

From Jan 1st 2017, three phase electric induction motors with a rated output of 0.75kW to 375kW and efficiency less than IE3 must be equipped with a variable speed drive (Inverter Drive). For exceptions, see EC Commission Regulation 640/2009.