WEG Automation CWM Series Three Pole Contactor to 105A (AC3) or 140A (AC1) for a Power Circuit to be switched by a 110V AC Control Circuit.
Rating:-
- Motor DOL Starter (AC3): 105A for a 55kW motor x 400V.
- Inverter or DC Thyristor Drive supply (AC1 - Thermal): 140A for up to 75kW x 400V.
Size 5: 75mm Wide x 126mm Deep x 117mm High. IP10. (155mm with front contacts)
Front-mounting external Auxiliary Contact adds 29mm to depth when fitted.
Side-mounting external Auxiliary Contact adds 11.5mm to width when fitted.
Mounting: 35mm DIN rail or 4 x 4.5mm slots at rear on 56-60mm x 90mm centres.
Terminals: Screw type. Max 50mm².
Weight: 1.5kg
Current Rating: 105A (AC3) or 140A (AC1)
Maximum Voltage: 690V 50/60Hz 1-3 Phase
Coil Voltage: 110V AC 50/60Hz x 255VA (pull-in), 13.1-19.1VA (sealing)
Main Contacts: 3 (NO)
Auxiliary Contacts, 1 x Normally Open (External, Front-mount). 1 x Normally Closed (External, Front-mount). Provision for 6 x additional external auxiliary contacts, see linked products below.
Standards: IEC/EN 60 947. DIN VDE 0660. UL. CSA
Lifespan (Electrical): 1,100,000 operations.
Lifespan (Mechanical): 10,000,000 operations.
Note:-
- AC1 Current Rating is for use with applications where open and closing operations are current free and the Current rating is not exceeded at any time.
- AC3 kW Rating is based on standard 2 pole or 4 pole motors.
- Coil connections can be made at either the top or bottom of the contactor to simplify replacement of existing contactors.
Manufacturer Part Number is CWM105-11-30D13 (10045570)