Delta Electronics REG2000 Series Universal Energy Recovery Regenerative Unit and loose DC Choke, to absorb 7.5W for use with any 400V 3 ph Inverter having access to DC+ and DC- terminals. Simple to set-up and provides continuous braking for any Make of existing drive.
Rating: 7.5kW for 60 seconds every 5 minutes.
Overload: 11.25kW for 10 seconds every 100 seconds.
Continuous Rating: 6kW.
Input Current: 12.8A DC at Rating.
Output Current: 10.5A at Rating.
Activation Voltage: 580V to 720VDC (adjustable via setting Pr.01-08).
Mains Voltage: 3 Phase AC 380V to 480V ( -15% +10%).
Frequency: 50/60Hz with tolerance to 47~63Hz.
Fuse Required: 100A maximum in the three phase supply.
Features: 5 x Digital Inputs, 2 x Digital outputs, 1 x c/o Relay 24V signal supply to 200mA and 2 x RJ45 Modbus RS485 and RTU.
Standards: CE Compliant, UL Certified Safety USA & Canada E176972 and KC Certiification.
Dimensions: REG2000 Frame A1 130mm Wide x 190mm Deep x 370mm high.
Enclosure Rating: IP20/NEMA1
Heat Loss: 204W
Ambient Temperature: Rated at 40°C with cover or 50°C without.
Weight: 7.5kg.
Dimensions: Choke 75mm x 86mm x 158mm deep.
Heat Loss: 5W
Weight: 0.84kg
Part Number: REG075A43A-21 + RG-RC075D2
Download the REG2000 Manual, Brochure, Datasheet and DC Choke Drawing from the links below: -