Vacon 100 Industrial Series AC IP21 Inverter for 30kW (40HP) 400V 3 Ph Centrifugal Fan or Pump in VxF or Sensorless Vector control to 61A. Converts fixed frequency three phase 400V input to variable frequency three phase 400V to control the speed of a standard AC Induction motor or permanent magnet synchronous motor.
Graphical Keypad, 2 x Analogue Inputs, 6 x Digital Inputs, 1 x Analogue Output, 3 x Relay Contact set, Modbus RTU (RS485), Modbus TCP (Ethernet).
Options fitted
Slot C: (SCB4) 1 x AI, 2 x AO (isolated)
Slot D: (SDB5) 3 x RO
Slot E: (SEBJ) Safe Torque Off (STO) / Safe Stop 1 (SS1) / ATEX
FL04: English, German, Polish, Russian, Czech, Slovak, Lithuanian, Latvian Language pack
DPAP: Safety Guide, Operating Guide (former VACON Installation Manual), guid- ance on effectively finding all documentation on Danfoss.com
DLPL: Polish
FBIE: PROFINET IO and EtherNet/IP single port
Size MR6: 195mm Wide x 229mm Deep x 557mm High. IP21/UL Type 1.
Weight: 20kg.
Overload: 110% x 60 seconds every 10 minutes
Speed Control Range: 0-320Hz
Braking: None
Input Current: [as output current]
Input Voltage: 380-500V ±10% Three Phase at 50-60Hz -5% +10%
EMC Filters to IEC EN61800-3 Category C2 1st and 2nd Environment (Industrial and Domestic). EMC filters can be disabled if required.
Wall mount in clean environment or cubicle mount.
Rated 40°C Ambient.
Ventilation space in above: 160mm
Ventilation space below: 80mm
Ventilation space at sides: 20mm
Heat Loss at max output: [not specified]
Mounting via 4 x 9mm diameter holes at rear on 148mm x 541mm centres.
Manufacturer part number is VACON0100-3L-0061-5+SCB4+SDB5+SEBJ+FL04+DPAP+DLPL+FBIE
Download the Vacon 100 Flow Manual and Brochure from the links below:-