Toshiba Tosvert VF-PS1 Series AC Frequency Inverter for 22kW (30HP) 400V 3 Ph Fan/Pump in VxF or Sensorless Vector control to 48A. Simple set-up and ready to run from its default settings.
Size F: 240mm Wide x 420mm High x 212mm Deep. IP00
Overload - 120% x 60 seconds, 135% x 2 seconds.
Speed Control Range - 0-500Hz.
Braking - To 13.3 Ohm minimum external resistor (not supplied) - use the 'Which Resistor' button on this page.
Features - 3 x Analogue Inputs, 6 Digital Inputs, 2 Analogue Outputs, 2 Digital Outputs and one relay output. RS-485 Modbus communication port.
'Safe Torque Off' (STO) function to SIL 2.
Input Current - 50A
Input Voltage - 380-480V Three Phase + 10% - 15% at 50/60Hz ± 5%
EMC Filters to IEC61800-3 Category C3, EN55011 Class A Group 2 (Industrial)
Wall mount in clean environment or cubicle mount.
Rated at 40C Ambient.
Ventilation space above and below - 100mm.
Ventilation space at sides - 50mm (0mm when top cover removed).
Heat Loss at max output - 720W.
Mounting via 4 x 6mm bolts on 206mm x 403mm centres at rear
Full part number is - VFPS1-4220PL-WP
Download the VFPS1 Manual from the link below:-