Schneider Altivar 71 (ATV71) series AC Inverter for 90kW (125Hp) 400V 3 Ph motor in VxF, Sensorless Vector or Full Closed-loop Flux Vector (when the optional Encoder Feedback card is fitted) control to 179A.
320mm Wide x 377mm Deep x 920mm High. IP20.
Weight: 60kg.
Overload: 150% x 60 seconds, 165% x 2 seconds.
Speed Control Range: 0.1-500Hz
Braking: to 4 Ohm minimum external resistor (not supplied) - See the Resistor options linked below or use the 'Which Resistor' button on this page.
3 Analogue Inputs, 1 Analogue Output, 1 Analogue/Digital Output, 6 Digital Inputs, 2 Relay Contact sets, RJ45 port for Modbus or CANopen communications. DC Bus terminals for DC supply or common bus energy saving applications.
Input Current: 175A
Input Voltage: 380-480V Three Phase -15% +10% at 50-60Hz ±5%
EMC Filters:
Wall mount in clean environment or cubicle mount.
Rated 50°C Ambient.
Ventilation space in front: 10mm.
Ventilation space above and below: 100mm.
Ventilation space at sides: 50mm (0mm with top vent cover removed).
Heat Loss at max output: xxxW.
Mounting via x x xmm diameter holes at rear on xxxmm x xxxmm centres.
Manufacturer part number is ATV71HD90N4. Previously sold under the Telemecanique brand.
Download the Schneider Electric Altivar ATV 71 Installation Manual and Quick Start Guide from the links below:-