Santerno Sinus Penta Series AC Inverter for 150kW (200HP) 400V 3 Ph motor to 260A in High Overload, or 220kW to 375A in Light Overload. Operates in VxF, Sensorless Vector or full closed-loop Flux Vector (when the optional encoder card is fitted). Converts fixed frequency three phase 400V input to variable frequency three phase 400V for a standard AC Induction motor.
Size S41 - 500mm Wide x 409mm Deep x 882mm High. IP00.
Weight: 121kg.
Light Overload: 220kW, 120% x 60seconds
Standard Overload: 220kW, 140% x 60 seconds.
Heavy Overload: 185kW, 175% x 60 seconds.
Strong Overload: 150kW; 200% x 60 seconds.
Speed Control Range: 0-1000Hz.
3 Analogue Inputs, 3 Analogue Outputs, 8 Digital Inputs, 2 Digital Outputs, 2 Relay Contact Sets, Modbus RTU Communications.
Input Voltage: 380-500V Three Phase at 50-60Hz
EMC Filters: EN 61800-3 issue 2 Second Environment Category C3 (Industrial).
Brake Module: Not Fitted.
Keypad included.
Cubicle Mount via 6 x 12mm holes using M8-M10 fastening screws.
Minimum clearence: 300mm above, 200mm below, 50mm either side or between drives.
Rated 40°C Ambient.
Heat Loss at max output: 3450W.
Manufacturer part number: SINUS PENTA 0217 4T XA2K0 S41.
Download the Sinus Penta User Manual and Installation Guide from the link below:-