SSD 690P AC Frequency Inverter for 132kW (175HP) 400V 3 Ph motor to 250A at high overload (Heavy Duty) or 150kW (200HP) to 302A when Fan/Pump rated, operates in VxF, Sensorless Flux Vector or Full Closed Loop Flux Vector control (when the optional encoder board is fitted). Includes 6901 Keypad.
Simple set-up and ready to run in VxF from its default settings.
Requires external choke - part number CO389936U401 (not included - see linked products below)
Size G - 455mm Wide x 465mm Deep x 1384mm High plus space required at sides for bars and above for roof mounting fan.
Weight - 108kg
Overload - 150% x 60 seconds and 180% for 0.5seconds at high overload rating or 110% for 10 seconds for fan/pump rating.
Switching frequency - 2.5kHz at full output, reducing to 1.2kHz at maximum overload.
Speed Control Range - 0/250Hz at continuous rating, or 120Hz if used to maximum overload.
Braking - Supplied with unit
4 x Analogue Inputs, 8 Digital Inputs, 3 Analogue outputs, 3 Digital outputs (relay contacts).
Input Current - 236A at high overload or 297A when Fan/Pump rating set.
Input Voltage - 380/460V three phase +-10% at 50/60Hz.
Input fuse - 300A at high overload or 350A when Fan/Pump rating set - to suit input bridge at 304000A²s
Cubicle mounting.
Rated at 40C Ambient.
Ventilation fan requires a separate 230V supply fused at 2A.
Heat Loss at max output - 2912W at high overload and 3482W when Fan/Pump rating set.
Full part number is - 690-433250G2-B00P00-A400 (was - 690PG/1320/400/0011/UK/0/0/0/0/B0/230/0). - Exactly the same as SSD Drives and Eurotherm Drives - 690PG-1320-400-0011-UK-0-0-0-0-B0-230-0.
The menu uses simple to understand English-language terms to describe its selection and functions. The default is English, but can be changed to German, French, Spanish, Italian, Polish, Swedish and Portuguese, by going to 'System', then 'Languages' and selecting the language required.
Download the 690P Technical and Software Manual from the links below...