SSD 690+ AC Frequency Inverter for 90 kW (120HP) 400V 3 Ph motor to 180A at high overload or 110 kW (150HP) to 205A when Fan/Pump rated, operates in VxF, Sensorless Flux Vector or Full Closed Loop Flux Vector control (when the optional encoder board is fitted). Simple set-up and ready to run in VxF from its default settings.
Size F - 257mm Wide x 355mm Deep x 720mm High overall.
Weight - 41kg
Overload - 150% x 60 seconds and 180% for 0.5seconds.
Speed Control Range - 0/120Hz (default), 0/240Hz or 0/480Hz.
Braking - none. (Unit supplied with braking)
No longer supplied without braking which can be ignored if not required.
4 x Analogue Inputs, 8 Digital Inputs, 3 Analogue outputs, 3 Digital outputs (relay contacts).
Input Current - 164A at high overload or 195A when Fan/Pump rating set.
Input Voltage - 380/460V three phase +-10% at 50/60Hz.
Input fuse - 200A at high overload and when Fan/Pump rating set - to suit input bridge at 100000A²s
Wall mount in clean environment or cubicle mount.
Rated at 40C Ambient.
Ventilation fan is 140W requiring a separate 230V supply fused at 3A.
Ventilation space above and below - 70mm.
Ventilation space at sides - 25mm.
Heat Loss at max output - 1950W at high overload and when Fan/Pump rating set.
Mounting - M6 screw fixings on 150mm x 700mm centres.
Full part number is - 690PF-0900-400-0011-UK-0-0-0-0-00-230-0. - Exactly the same as SSD Drives and Eurotherm Drives - 690PF-0900-400-0010-UK-0-0-0-0-00-230-0.
The menu uses simple to understand English-language terms to describe its selection and functions. The default is English, but can be changed to German, French, Spanish, Italian, Polish, Swedish and Portuguese, by going to 'System', then 'Languages' and selecting the language required.