LSLV S100 series AC Inverter for 11kW (15HP) 400V 3 Ph motor to 24A at high overload. Operates in VxF or Sensorless Vector mode and converts fixed frequency three phase 400V input to variable frequency three phase 400V to control the speed of a standard AC induction motor.
Size 4: 300mm Wide x 264mm Deep x 460mm High. IP66
Weight: 9.6kg.
Front Mounted Mains Disconnect Switch (SW)
Overload: 150% x 60 seconds, (High Overload)Overload: 120% x 60 seconds (Fan/Pump rated)
Speed Control Range: 0-400Hz
Braking (DBr): Minimum 40 Ohm minimum external resistor (not supplied) - use the 'Which Resistor' button on this page.
Built-in Safe Torque Off (STO)
Integrated Keypad, 2 Analogue Inputs, 5 Digital Inputs, 1 Analogue Outputs, 1 Digital Output, 1 Relay Contact sets, DC Bus +/- Terminals.
'Safe Torque Off' (STO) function to SIL 2 (EN 61508) via Digital Input.
Input Current: 26.5A (high overload),
Input Voltage: 380-480V Three Phase +10% -15% at 50-60Hz ±5%
EMC Compliance: IEC EN 61800-3 Category C3, (Class A) Industrial. Can Be disabled via connector switch if nescessary.
Wall mount.
Rated 50°C Ambient (high overload), 40°C ambient (fan/pump rated).
Ventilation space in front: 50mm.
Ventilation space above and below: 100mm.
Ventilation space at sides: 50mm
Ventilation space between: 50mm.
Heat Loss at max output: [not specified]
Manufacturer part number is LSLV0110S100-4EXFNS (LV0110S100-4EXFNS)
Download the LS S100 Manual from the links below:-