IMO HD2IP Series AC Inverter for 15kW 400V 3 Ph motor to 32A at High Overload or 18.5kW to 38A when Fan/Pump rated.
Operates in VxF, Sensorless Vector or Full Closed-loop Vector control (with the optional encoder feedback card) and converts fixed frequency Three Phase 400V input to variable frequency Three Phase 400V to control a standard AC induction or permanent magnet synchronous motor.
Size 2: 223mm Wide x 251mm Deep x 475mm High.
IP55 with Mains Isloator (SW)
Weight: 13kg.
Output: 32A (High Overload); 38A (Fan/Pump)
Overload: 150% for 60 seconds. 200% for 1 second (High Overload); 120% for 60 seconds. (Fan/Pump)
Speed Control Range: 0-400Hz.
Braking (DBr): Built-in Braking Transistor. A 23Ohm (minimum), 32 Ohm (100% braking torque) external resistor is required for Dynamic Braking. Resistor is not supplied and should only be fitted if this feature is required. Resistor option given below.
LCD Multi-line Operator Keypad with Real Time Clock. (No batteries supplied)
2 Analogue Inputs, 6 Digital Inputs (2 Pulse Inputs), 1 Analogue Output, 2 Digital Output (1 Pulse Output), 2 Relay Outputs (Change-over)
Serial Communications: Terminals for Modbus RS485
Safe Torque Off (STO) function to SIL2 (EN61800-5-2)
3 Option Slots available. See option cards below.
Input Current: 40A (High Overload), 45A (Fan/Pump)
Input Voltage: 380-480V Three Phase -15% +10% at 50-60Hz ±5%.
EMC Filter: IEC EN 61800-3 Category C3 (Industrial). Earth connection can be removed if required.
Wall mount.
Rated ambient: 40°C. Maximum ambient: 50°C (De-rate required above 40°C)
Ventilation space in front: [not specified], above: 100mm, below: 100mm, at sides: 100mm
Heat Loss at max output: xxW
Mount with 4 x M6 bolts (not supplied) at rear on 187mm x 459mm centres.
Manufacturer part number is HD2IP-32A-43